Thank you for taking an interest in Spd Electrical Systems Inc part number ETM4039, which is currently available for purchase today here on ASAP Aerospace. You have reached our Request for Quote (RFQ) page for this part number ETM4039, where we make it easy to secure competitive pricing and procurement options from our staff.
Part Number ETM4039 Details:
Part number ETM4039 traces back to Spd Electrical Systems Inc (CAGE Code 30086), having been classified under NSN 5925007836221 and item name Circuit Breaker. With its NSN, this part number belongs to FSG 59 Electrical and Electronic Equipment Components and FSC 5925 Circuit Breakers. Additional listing data derived from the NSN includes the NIIN 007836221, the INC 00136, and NCB code 00 (USA).
Note : We Will Not Share Your Information To Any Third Parties.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-783-6221 Item PartTypeName: CIRCUIT BREAKER | 5925 | 007836221 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
ETM4039 | 2 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 90.0 AMPERES AC AND 90.0 AMPERES DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC AND 10000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 47.000 MINIMUM AT 200 PCT AND 110.000 MAXIMUM AT 200 PCT AND 14.000 MINIMUM AT 300 PCT AND 29.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |